ABB CPS6000 Product Manual page 162

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Rectifier Management
obj,attr
description
gm1,fsp
Rectifier float set-point
gm1,bsp
Rectifier boost set-point
gm1,rme
Redundancy monitor enable
Rectifier Float Set-point: The voltage at which the plant will float charge the battery strings.
Rectifier Boost Set-point: The voltage at which the plant will boost charge the battery strings.
Redundancy Monitor Enable: Activates the Redundancy Loss alarm feature.
Rectifiers
obj,attr
description
gsr,stt
Individual rectifier state
gsr,adc
Individual rectifier current
Individual Rectifier State: When requested, shows the state of the individual rectifiers. Note that the
rectifier numbering starts from the left-most position of the master shelf (shelf number 1.)
When obtaining individual rectifier status information, the following information may be transmitted:
ON: Rectifier operating normally. User may use ope to turn ON a rectifier in standby.
OFF: Rectifier has been shutdown due to hardware failure.
STANDBY: User has inhibited the rectifier's output voltage. User may use ope to place a rectifier into a standby
condition.
MISSING: An acknowledged rectifier has been removed.
VACANT: Rectifier has not been installed in that position.
Rectifiers may also be put in standby; however, the ability to place rectifiers in standby requires some
backup plan to take the rectifier out of standby automatically under a low voltage condition. The
battery on discharge (BOD) threshold is used as a rectifier-on voltage threshold. In other words, when
the plant voltage dips below the BOD threshold, the controller turns on all rectifiers that are in standby.
Individual Rectifier Current: When requested, shows the current output from an individual rectifier.
Page 162
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
x
x
x
x
x
x
Related Commands
sta
cha
ope
r
x
x
type
range of values
number
51-56.5, 54.5 V
number
54-56.5, 55.2 V
number
0: disable, 1: enable
type
range of values
"ON", "OFF", "STANDBY",
"MISSING"
text
Only "ON" and
"STANDBY" can be used
with ope.
number
ddd