sum
Report Battery Discharge Statistics (profile)
Syntax:
sum dc1,bod
Description
This command reports the last battery discharge profile report. The report includes cleared date and
time, start date and time, end date and time, duration in seconds, and up to 50 sample points. Each
sample is time stamped in seconds. We compress the samples to derive a minimum set of data
required to reconstruct the curve while retaining important coup de fouet minimum and maximum
voltages and lowest voltage at end of discharge. The following is an example of a command response:
* sum dc1,bod
:DC1 BOD
CLR=29-JUN-04,10:27:11 BEG=30-JUN-04,10:38:36 END=30-JUN-04,10:42:53 DUR=256
VAL= 0,51.08
8,50.18
18,49.24
20,48.87
248,48.36
252,49.76
254,50.84
256,51.13
.
*
The "." line is the end-of-command identifier. The "* " in the example above is the user command line