Availability of du/dt filter and common mode filter by drive or inverter type

Product type
ACS880-104LC
ACS880-107LC

Additional requirements for explosion-safe (EX) motors

If you will use an explosion-safe (EX) motor, follow the rules in the requirements table above.
In addition, consult the motor manufacturer for any further requirements.
Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and
AM_
Use the selection criteria given for non-ABB motors.

Additional requirements for braking applications

When the motor brakes the machinery, the intermediate circuit DC voltage of the drive
increases, the effect being similar to increasing the motor supply voltage by up to 20 percent.
Consider this voltage increase when specifying the motor insulation requirements if the
motor will be braking a large part of its operation time.
Example: Motor insulation requirement for a 400 V AC line voltage application must be
selected as if the drive were supplied with 480 V.
Additional requirements for drives with an IGBT supply unit or regenerative rectifier
unit
It is possible to increase the intermediate circuit DC voltage from the nominal (standard)
level with a parameter in the supply unit control program. If you choose to do this, select
the motor insulation system which withstands the increased DC voltage level.

Additional requirements for ABB high-output and IP23 motors

The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347 (2001).
This table shows the requirements for protecting the motor insulation and bearings in drive
systems for ABB random-wound motor series (for example, M3AA, M3AP and M3BP).
Nominal AC supply
voltage
Motor insulation
U
≤ 500 V
Standard
N
500 V < U
≤ 600 V
Standard
N
or
Reinforced
600 V < U
≤ 690 V
Reinforced
N
Availability of du/dt filter
Standard
Standard
ABB du/dt and common mode filters, insulated N-end motor
system
P
< 100 kW
N
P
< 140 hp
N
-
+ du/dt
-
+ du/dt
Electrical planning guidelines 21
Availability of common mode filter
Requirement for
bearings
100 kW ≤ P
N
200 kW
140 hp ≤ P
N
268 hp
+ N
+ du/dt + N
+ N
+ du/dt + N
(CMF)
Standard
Standard
<
P
≥ 200 kW
N
<
P
≥ 268 hp
N
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF