Releasing the latch Handle
Press Latch/Handle
Release Button In
Latch /Handle in
Latched Position
Installing / Removing the Rectifier

Ringer Installation

Install the Ringer Chassis and Ringer Modules
This procedure is used to install ringer chassis's and ringer modules in the CPS6000 shelf. Figure 5-16
shows a shelf, Ringer chassis and a Distribution Module. Up to two Ringer Chassis's may be installed
per shelf, one in each of the two right-most power slots to the left of the Distribution Section. Each
Ringer chassis accepts two ringer modules, a primary and a spare. For redundant ringing, install both
Primary and Spare Ringers in each Ringer Chassis. The Ringer chassis and ringer modules are shipped
separate.
Warning: Consider the Ring signal as hazardous voltage.
Warning: Ringer chassis's and Ringer modules will be powered when installed in the shelf when
rectifiers and/or battery power is present.
Note: Ringer output connections are made after ringers are seated in the Ringer chassis.
Note: The primary and spare Ringer modules install facing opposite directions.
Note: No rectifiers may be installed to the right of a Ringer Chassis.
Page 56
© Copyright 2021 ABB. All rights reserved.
To Install : Release the latch/handle.
Push the rectifier in firmly until seated.
The latch/handle will pop most the way up.
Push the latch/handle back into the latch position
To Remove : Release the latch/handle.
Push the latch/handle all the way down (shown)
Pull the rectifier out by the latch/handle.
Figure 5-15: Rectifier Installation
Latch/Handle
Springs Out
Part Way
Latch/Handle
Rotated All the
Way Down