Configure Additional Battery Inputs (optional)
Configure the distribution panel for the additional battery inputs as required, in groups of four.
Step
Action
1.
Remove breaker terminal posts in groups of four.
2.
Install busbars.
Remove jumpers and reinstall as shown to separate the alarm contacts between the battery input and
3.
load output sections.
If optional internal battery switches are required:
Install 1, 2, or 3 pole battery switches as required to match battery discharge current. Make sure switch is
down, in the OFF position.
4.
If optional internal battery switches are not required:
Install no-switch jumper busses as required.
5.
Using a voltmeter, verify polarity of the battery cables.
6.
Attach the POSITIVE cable to the RTN bus position in line with the switch.
7.
Attach the NEGATIVE cable to the busbar directly above the switch.
8.
Using a voltmeter, verify polarity of the battery connection between the RTN and battery input bus.
9.
Leave the switch in the OFF position until the unit is ready to be energized.