ABB CPS6000 Product Manual page 194

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Description
obj
Battery On
bda1
Discharge
Very Low
vla1
Voltage
Single AC Fail
acf1
Battery Test
bts1
Active
Multiple
mrfa1
Rectifier
Failure
Redundancy
rls1
Loss
Single
rfa1
Rectifier Fail
Multiple AC
macf1
Fail
High Battery
bta1
Temp
Major Fuse
faj1
Alarm
The following commands will help set up the programmable alarm relays as per the CPS4000 scheme.
No changes to default for thermal probe or contactor open alarms.
ES648A
cha faj1,acc=R3
cha mrfa1,acc=""
cha bts1,acc=""
cha macf1,acc=R4
cha macf1,sev=MAJ
cha vla1,acc=""
cha vla1,sev=RO
cha rls1,acc=""
cha rfa1,sev=MIN
cha rfa1,acc=""
cha bta1,sev=MAJ
Page 194
© Copyright 2021 ABB. All rights reserved.
Default
R1
MAJ
R1
R1
MAJ
""
R2
MIN
R2
R4
RO
""
R3
MAJ
""
R3
MIN
""
""
MAJ
""
R2
MAJ
R4
""
MIN
""
""
MAJ
R3
Comments
Enable relay R3 as Major Fuse Alarm
Disable relay R3 as Multiple Rectifier Fail alarm
Disable relay R4 as Plant Battery Test Active
Enable relay R4 as Multiple AC Fail
Multiple AC Fail is MAJ
Disable relay R1 as Very Low Voltage alarm
Change Very Low Voltage alarm from MAJ to RO
Disable relay R3 as Redundancy Loss
Change Single Rectifier Failure to MIN
Disable all relays for Single Rectifier Fail alarm
Change High Battery Temperature from MIN to MAJ
ES648A
ES648B
MAJ
R1
RO
R4
MIN
R2
RO
""
MAJ
""
MIN
""
MIN
""
MAJ
""
MAJ
""
MAJ
R3
Comments
Need to change to RO on
RO
ES648
MAJ
Changes for both versions
MIN
No change from default
Disable relay R4 as Battery
RO
Test Active
Disable relay R3 as Multiple Rect.
MIN
Fail
Disable relay R3 as
MIN
Redundancy Loss
Change from MAJ to MIN for
MIN
both versions
MIN
Changes to both versions
Change from MIN to MAJ for
MAJ
both versions
Relay R3 is Major Fuse alarm for
MAJ
both versions