ABB CPS6000 Product Manual page 97

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

System Settings: Menus for configuring the following system parameters:
Display Contrast
System Date and Time
Daylight Savings
Display T Units
High Ambient T
Low Ambient T
Communication Ports: Menus for configuring the following communication parameters:
Port Type
Local Port Settings
Modem Port Settings
Page 97
© Copyright 2021 ABB. All rights reserved.
Allows display backlight intensity to be adjusted for contrast in local ambient light. Factory
default is 50%.
Set date in yyyy-mm-dd and time in hh:mm:ss format.
Enable or disable. Factory default is Enabled.
Display temperature status in C or °F. Factory default is C.
High temperature alarm threshold that can be set from 35°C to 75°C. The factory default
setting is 75°C.
Low temperature alarm threshold that can be set from -40°C to 10°C. The factory default
setting is -40°C.
Set the communication port to either Local or Modem. Factory default is Local.
Enable or disable Write Access, the ability to change system settings through the local port.
The factory default setting is enabled.
Set the port Baud Rate to auto, 2400, 4800, 9600 or 19200. The factory default setting is
auto.
Set port Flow Control to none, HW (hardware) or SW (software). The factory default setting
is none.
Enable or disable Write Access, the ability to change system settings through the modem.
The factory default setting is enabled.
Set the port Baud Rate to 2400, 4800, 9600 or 19200. The factory default setting is 2400.
Set port Flow Control to none or SW (software). The factory default setting is none.
Set the number of rings to be detected by the modem before it answers (Rings to
Answer). Can be set from 1 to 9. The factory default setting is 1.