Connectors
Figure 7-2 shows a side view of the controller unit.
A ground referenced RS-232 connector (J3) serial port is available for serial connection to a PC using
EasyView or standard terminal emulation for craft programming and retrieving status locally. This port
can also be used to an external modem for remote access or with the EBW Network Interface Card
known as the Gateway to provide a second Ethernet port. The Ethernet ports are compatible with ABB
Power Galaxy Manager used for web-based remote access and network management. This serial port
can also be used to provide local access or for a connection to an external modem in non-NX400
systems.
Ethernet connector P6 is brought out to the RJ45 attached at the front of the unit. This port can also
serve a local Craft port by configuring the controller to place this port into Server mode. In this mode
the port serves as the Ethernet Craft port and allows standard Web browsers to be used for accessing
the controller. This port should never be plugged into the office LAN if it is in the DHCP Server mode.
Factory default for this port operation is "Static" requiring an IP address to be programmed for the
unit.
Connector P5 is used for the 1-Wire management options. J1 provides all the office alarms that are
brought out to the unit with various cable options. Included in this alarm interface are six Form-C alarm
relays. Two are pre-assigned as Power Major (Impaired) and Power Minor (degraded) alarm relays. The
four remaining relays are available as user-definable alarms and have been predefined in the standard
controller.
Software
The software is functionally divided on the Main Menu into the following categories:
Alarms
Warnings
Status
Control/Operations
History
Configuration