ABB CPS6000 Product Manual page 29

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

ABB Power
Model Number
of Rectifier
Rectifier (A)
20A
QS852A
25A
QS853A
25/30A
QS862A
40A
QS864A
50A
QS865A
*Conduit and further temperature deratings may be required in some installations .Cross-check table with local code and regulation requirements
Thermal Compensation
Thermal Compensation: For thermal compensation, the QS873A Voltage/Thermal probe (VT-Probe)
and its associated cables must be ordered. Refer to Section 5 for details on their interconnection, and
Section 9 for more information on VT-Probes. The probe is provided with a weatherproof case.
Thermal Compensation/Voltage Monitoring: When voltage monitoring for battery string voltage
imbalance detection is to be implemented in addition to thermal compensation, the VT-probe and its
associated cables must be ordered. Refer to Section 5 for details on their interconnection, and Section
9 for more information on VT-Probes and voltage monitoring.
Page 29
© Copyright 2021 ABB. All rights reserved.
Number of
Nominal Input
Rectifiers per
Voltage
AC feed
208
1
208
2
208
3
208
4
208
5
208
1
208
2
208
3
208
4
208
5
120
1
120
2
120
3
208
1
208
2
208
3
208
4
208
1
208
2
208
3
208
1
208
2
Table 3-A: Rectifier AC Input Current Table (continued)
Minimum Circuit
Breaker value
Nominal AC
recommended
Current (A)
(A)*
6
15
12
15
18
25
24
30
30
40
7.4
15
14.8
20
22.2
30
29.6
40
37.0
50
13.0
20
26.0
35
39.1
50
8.8
15
17.6
25
26.4
35
35.3
45
11.8
15
23.5
30
35.3
45
14.5
20
29.1
40
75°C Minimum
Recommended
Wire Gauge
(AWG)*
14
14
10
10
8
14
12
10
8
8
12
8
8
14
10
8
8
14
10
8
12
8