ABB CPS6000 Product Manual page 186

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Alarm /
Description
Event
Alarm issued when an
external disconnect
switch produces an
open charge path to
batteries in the
Open
Distribution Module.
String
This alarm is only
available when used
with the QS872A Board
is in the system
(connector P4).
Alarm asserted when
the total rectifier
output current exceeds
N rectifier capacity
Rectifier
value. The feature must
Redundanc
be enabled and
y Loss
assumes N+1 rectifiers
are present in the
system. Disabled by
default.
Reserve time low alarm
threshold configured
Reserve
for systems calculated
Time Low
back- up reserve has
been reached.
Alarm that is
automatically asserted
when the controller
Sense Fuse
senses the DC bus
voltage to be lower
than 35.5V +/- 0.5V.
Detection of a single
Single AC
rectifier reporting ACF
Fail
in the system.
Single
Detection of a single
Rectifier
rectifier failing in the
Fail
system.
The controller is not
receiving DC power
Un-powered
from the shelf. All Form
Controller
-C relays are de-
energized to assert
respective alarms.
Page 186
© Copyright 2021 ABB. All rights reserved.
Default
Range /
PMJ
Setting
Severity
Major/
Major
Minor/
RO
Enabled/
Disabled
Disabled
(Major/
/ Minor
Minor/
RO)
0-99.9
hours
0 hours
Major/
Minor
Minor/
RO
Major/
Major
Minor/
RO
Major/
Minor/
Minor
RO
Major/
Minor
Minor/
RO
N/A
N/A
Alarm Relays
PMN
Relay 1
Relay 2
Relay 3
LED
PMJ
PMN
NORM
Relay 4
Red
Yellow
Green
LED
AUX
MD
Red