ABB CPS6000 Product Manual page 149

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Controller
User Interface
LED
Display
(Note 3)
MIN, Battery
AMBER
High
Temperature
MIN, Thermal
AMBER
Probe Fail
MIN, Rectifier
AMBER
Fail
MIN, Minor
Communication
Fail
AMBER
(Single
Rectifier
signaling)
Page 149
© Copyright 2021 ABB. All rights reserved.
Rectifier LEDs
Ringer
(Note 4)
LED
AC DC
ALM
-R-
Distribution
Module
Possible Problem(s)
Board LED
Batteries have
exceeded temperature
threshold set by
user.
Battery thermal probe
failed.
Single rectifier thermal
alarm: Excessive
ambient temperature
Multiple rectifier
failure
Rectifier lost
communication with
controller.
Possible Solution(s)
Call your local field
representative.
1. Ensure thermal probe is
properly connected to
thermal probe cable.
2. Ensure cable is properly
connected to the rear of the
Distribution Module.
3. If problem persists, replace
thermal probe per ensuing
instructions.
4. If problem still persists, call
your local field
representative.
1. Verify that there is no
obstruction of the vertical
airflow path.
2. Reset the rectifier by
removing the rectifier,
waiting approximately 30
seconds, and replacing the
rectifier.
3. If problem persists, replace
the rectifier.
4. If problem still persists, call
your local field
representative.
1. If a rectifier has been
removed from an installed/
operational system, go to
the Control/Operations
menu and execute Uninstall
Equipment.
2. Reset the rectifier by
removing the rectifier,
waiting approximately 30
seconds, and replacing.
3. If problem persists, replace
the rectifier.
4. If problem still persists, call
your local field
representative.