ABB CPS6000 Product Manual page 28

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Ringer Output Cable
Ringer Cables one per Ringer Output (Ringer Chassis).
Item
Ringer Output Cable H569-470 G kit – 15' cable with connector for CPS6000/CPS2000 shelf on one
end and unterminated leads on the other end.
Ringer Output Cable – 150 ft
Commercial - Molex:
Plug 39-01-4031
Socket (3 per plug):
Terminal Type 5556
16 AWG 39-00-0079
18 AWG 39-00-0059
Tool 11-01-0197
Ringers
Up to two Ringers plug into a Ringer Chassis.
One Ringer per Ringer Chassis is non-redundant (simplex). Two Ringers per Ringer Chassis is 1 + 1
redundant (duplex).
QS820A Ringer
AC Power Cables
An ac power cable must be ordered. A standard ac cable set will not fit in the CPS6000 shelf. Verify that
the sum of the input currents for all the rectifiers served by an ac circuit breaker does not exceed 80%
of the breaker's rating.
ABB Power
Model Number
of Rectifier
Rectifier (A)
15A
QS861A
Page 28
© Copyright 2021 ABB. All rights reserved.
Ringer
Nominal Input
Voltage
120
120
120
120
120
208
208
208
208
208
Table 3-A: Rectifier AC Input Current Table
Number of
Nominal AC
Rectifiers per
Current (A)
AC feed
1
7.8
2
15.6
3
23.4
4
31.2
5
39.1
1
4.4
2
8.8
3
13.2
4
17.6
5
22.0
Ordering code
847922101
CC848804765
Commercial
Ordering code
108990082
Minimum Circuit
75°C Minimum
Breaker value
Recommended
recommended
Wire Gauge
(A)*
15
20
30
40
50
15
15
20
25
30
(AWG)*
14
12
10
8
8
14
14
12
10
10