COMPLETEDDischarge completed normally
TIMEOUTAuto discharge test timed out
DISABLEDAuto discharge test disabled
ENDVDischarge test hit end voltage
CANCELEDDischarge test canceled by user
lis
List Rectifiers
Syntax: lis rec
Description
This command is used to list all the rectifiers in the system. The command will list all present and
missing rectifiers. Missing rectifiers are rectifiers that have been removed from a shelf. The cle will
clear missing rectifiers from the controller's memory and they will no longer be listed by this command.
Return value for a system with 3 rectifiers on shelf 1 would look like the following:
* lis rec
G11
G12
G13
.
_
login
Log-in
Syntax: login "password"
where password is either the user, super-user or administrator password
Description
This command is used to log-in as a user, super-user or administrator. For example, if you are currently
logged into the controller as a user but would like to change the site id you must first use this
command to log-in as a super-user. You must be logged in as an administrator in order to upgrade the
software and change passwords.
ope
Operate a control
Syntax: ope obj,attr=value
where: obj,attr is an object-attribute pair. For example, dc1,pbt.
Description
This command is used to operate a system control parameter. Examples are listed below to illustrate
how this command works.
ope ps1,usl=1Update serial link
ope dc1,stt="boost"Place plant into boost mode
You must be logged in as a super-user to use this command.