-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Power System
obj,attr
description
ps1,des
Power system description
ps1,sid
Site ID
ps1,swv
Software version
ps1,ltt
Lamp test
ps1,usl
Update serial link
ps1,amt
System ambient temperature
ps1,ptt
Communication port type
ps1,dls
Daylight savings time enable
ps1,tim
Time
ps1,dat
Date
Site ID: If desired, you may type in a maximum 15 alpha-numeric character set to uniquely define a site
location.
Update Serial Link: Running this command allows the system controller to retake inventory of using
equipment. Use this command to update acknowledged equipment when, for example, a system is to
run with one less rectifier.
DC Plant
obj,attr
description
dc1,stt
Plant state
dc1,vdc
Plant voltage
dc1,adc
External Battery Shunt Size
dc1,sha1
Plant shunt size
dc1,trd
Plant total rectifier drain
dc1,isd
Imminent shutdown enable
dc1,cap
Total rectifier capacity
dc1,rss
Rectifier restart
dc1,bod
Battery on discharge
Plant State: The plant is normally in the float-charge mode; however, the super-user may instruct the
plant to enter the boost-charge mode.
Plant Voltage: The voltage of the plant at the time of querying.
Plant Current: The current being drawn by the load at the time of querying.
External Battery Shunt Size: External battery shunt amp rating.
Plant Total Rectifier Drain: The current being drawn by the battery and load from the plant at the time
of querying.
Imminent Shutdown Enable: Factory shipped disabled. When enabled, prior to disconnecting of LVD
contactor during battery discharge, the controller will transmit the Imminent Shutdown alarm to the
host indicating batteries will disconnect from the load in 15 seconds. See Imminent Shutdown in
Section 6 for more details on this feature.
Total Rectifier Capacity: Sum of the rated outputs of installed rectifiers.
Page 157
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
type
x
text
x
x
text
x
text
x
number
x
number
x
number
x
x
text
x
x
number
x
x
time
x
x
date
Related Commands
sta
cha
ope
type
text
x
x
number
x
number
x
number
x
x
number
x
number
x
x
number
x
number
x
x
number
x
range of values
"QS840A"
Up to 15 characters:""
ACU software version
1: do lamp test
1:perform update serial link
dd°C
"LOCAL", "MODEM"
0: disable, 1: enable
hh:mm:ss (24-hour format)
dd-mm-yy
range of values
"FLOAT", "BOOST"
dd.dd V
ddd.d A
0-9999: 200, 0: none
ddd.d A
0: disable, 1: enable
ddd.dA
0:no action 1:restart
0:on discharge, 1: not on discharge