ES648B
cha faj1,acc=R3
cha mrfa1,acc=""
cha mrfa1,sev=MIN
cha bts1,acc=""
cha vla1,acc=R4
cha macfl,acc=""
cha macfl,sev=MIN
cha bda1,sev=RO
cha rls1,acc=""
cha rfa1,sev=MIN
cha rfa1,acc=""
cha bta1,sev=MAJ
Page 195
© Copyright 2021 ABB. All rights reserved.
Comments
Enable relay R3 as Major Fuse Alarm
Disable relay R3 as Multiple Rectifier Fail alarm
Change Multiple Rectifier Failure from MAJ to MIN
Disable relay R4 as Plant Battery Test Active
Enable relay R4 as Low Voltage Alarm
Disable relay R2 as Multiple AC Fail
Change Multiple Rectifier Failure to MIN
Change Battery On Discharge from PMJ to RO
Disable relay R3 as Redundancy Loss
Change Single Rectifier Failure to MIN
Disable all relays for Single Rectifier Fail alarm
Change High Battery Temperature from MIN to MAJ