22-position external distribution panel
Overview
The J5694722 external distribution accepts up to 22 bullet-breakers for DC loads and occupies 3U of
vertical rack space in a 23î rack. The panel has a total output capacity of 400A and is front accessible.
The following configurations are available in 3 distinct distribution modules:
Without contactor
•
With 400A LVLD and 500A shunt
•
With 400A LVBD and 500A shunt
•
Features
Return Connection
Output Connections
Circuit breaker /
Battery Switch
Position
Up to 22 flexible battery positions that can be configured either with the battery bus or the load bus using an
•
adapter plate
All lug connections shall accept double-holed lugs.
•
Staggered vertical arrangement of up to three distributions directly stacked with wiring access.
•
Contactor control, measurements and alarms with the QS84x compatible ES772 module
•
CO ground connection
•
Contactor options ñ None, LVBD, LVLD
•
500A shunt
•
Accommodates single, double and triple pole breakers with lug adapter for multi-pole breakers
•
English hardware (1/4-20) for all customer connections
•
TPS fuses in place of bullet-breakers
•
Page 145
© Copyright 2021 ABB. All rights reserved.
18 Output (load)
4 Battery
Position
Figure 12-7: J5694722 External Distribution
Alarm Jumpers
Position