ABB CPS6000 Product Manual page 140

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Pin
Name
Definition
8
VPWR -
V(-) Power
9
STATUS1_RTN
Reference for STATUS1
10
STATUS1
Contactor 1 Status Monitor
Positive Battery Shunt
11
SHUNT+
Input
12
LVD1_COIL
Contactor 1 coil input
Trip-Indicator Input-2 for US Style CB or
13
DIST_ALM_2
GMT Fuse. Alarm on closure to VBus(- ).
Alarm input for external battery
14
EXT BAT SW2
disconnect switch; alarms on closure to
VBus(-).
Pin
Name
Definition
1
BATT2_SENSE
Polarity Sense for String 2.
2
STATUS2_RTN
Reference for STATUS 2.
3
STATUS2
Contactor 2 Status Monitor.
4
LVD2_COIL
Contactor 2 coil input.
Page 140
© Copyright 2021 ABB. All rights reserved.
Table 12-A: Connector J1 Pin-out Definitions (continued)
Table 12-B: Connector J3 Pin Definitions
Comments/Connections
Power for ES772A, connect to VBus(-)
Connect to C pin of micro switch of Contactor 1.
Connect to NO pin of micro switch of Contactor 1.
Polarity is during battery discharge
Connect to one side of Contactor 1 coil,
Connect to NC terminal of breaker micro switch or to
indicator lead of GMT fuse, other end (C) referenced to
VBus(-).
Connect to NC micro switch of US Style CB, other end (C)
referenced to VBus(-), micro switch must close upon
manual opening of CB.
Comments
Connect to battery negative VBus(-) of string 2.
Connect to C pin of micro switch of Contactor 2.
Connect to NO pin of micro switch of Contactor 2.
Connect to one side of Contactor 2 coil, other side of coil
connected to VBus(+).