ABB CPS6000 Product Manual page 185

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Alarm /
Description
Event
Controller has
determined that LVD 1
LV
has failed. The
Disconnect
contactor did not open
Contactor 1
or close when expected
Fail
or is asserting an alarm
in the closed state.
Low Voltage
LV
Disconnect Contactor 1
Disconnect
is in the Open state
Contactor 1
either through manual
Open
intervention or LVD
disconnect.
Controller has
determined that LVD 2
LV
has failed. The
Disconnect
contactor did not open
Contactor 2
or close when expected
Fail
or is asserting an alarm
in the closed state.
Low Voltage
LV
Disconnect Contactor
Disconnect
2 is in the Open state
Contactor 2
either through manual
intervention or LVD
Open
disconnect.
Condition asserted to
provide a remote
indication that a
Manual Or
battery test has been
Periodic
initiated either through
Battery
automatic means.
Test In
Automatic testing
Progress
must be enabled.
Factory default is
disabled.
Controller has detected
Monitoring
a failure in an attached
Module
remote monitoring
Failure
module.
Detection of two or
Multiple AC
more rectifiers
reporting ACF in the
Fail
system.
Multiple
Detection of two or
Rectifier
more rectifiers failing
Fail
in the system.
Page 185
© Copyright 2021 ABB. All rights reserved.
Default
Range /
PMJ
PMN
Setting
Severity
Major/
Major
Minor/
RO
Major/
Major
Minor/
RO
Major/
Major
Minor/
RO
Major/
Major
Minor/
RO
Major/
RO
Minor/
RO
Major/
Minor
Minor/
RO
Major/
Major
Minor/
RO
Major/
Major
Minor/
RO
Alarm Relays
Relay 1
Relay 2
Relay 3
Relay 4
LED
LED
AUX
PMJ
PMN
NORM
MD
Red
Yellow
Green
Red