Spare Ringer Module
Step
Action
Use Tip Jumper J12 to set the Ringer output type. See Figure 5-16 for J12 Tip Jumper location.
Note: Ringer output type is determined by connecting Ring Return (Tip) to Battery or Ground. External
7.
connection of Ring Return (TIP) to Battery or Ground may be used with J12 in EXTERNAL position. Ringer
output is disabled if Ring Return is not connected to Battery or to ground. See Section 10 for more
information on Ringing Types.
Ringing Type
Ground Backed
Battery Backed
Ground Backed – no-dc
Externally Selected
Warning: Consider the Ring signal as hazardous voltage.
8.
Connect Ringer loads using Molex 39-01-4031 connector, Socket Terminal to the HDR13 plug located
inside the Ringer Chassis at the bottom-front. See Figure 5- 18.
Route ringer load cables through upper or lower notches in Ringer chassis and distribution module
9.
chassis. See Figure 5-18.
Page 58
© Copyright 2021 ABB. All rights reserved.
Primary Ringer Module
Figure 5-17: Ringer Installation
Tip Jumper J12 Position
1. TIP BAT
2. TIP GND
2. TIP GND
3. EXTERNAL
1. TIP BAT
3. EXTERNAL
Ringer Chassis
Comments
Also requires Controller configuration of
dc Offset: Disabled
Requires external connection of Tip to
Battery or Ground.