ABB CPS6000 Product Manual page 166

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Call-Out
obj,attr
Description
p1,phn
Primary phone number
a1,phn
Alternate phone number
Ringer Plant
obj,attr
Description
Rp1,frq
Ringer output frequency
Rp1,vsp
Ringer boost voltage set-point
Rp1,ofe
Ringer offset enable
Rp1,va
Ringer output va
Additional T1.317 Commands
Ala
Report Active Alarms
Syntax:
ala
Description
This command reports all the active alarm conditions in the plant. One alarm message is listed per line
in the report. The table below lists the default alarm messages. Note that if user changes the severity
of the alarm, the corresponding change will show up in the alarm message. However, alarm conditions
with the RO severity will not be displayed, the rec command, discussed later, should be used.
Alarm Message
MAJ, Multiple Rectifier Fail
MAJ, Multiple AC Fail
MAJ, Battery On Discharge
MAJ, High Voltage
MAJ, Sense Fuse
MAJ, Fuse Major
MAJ, Auxiliary Major
MAJ, Contactor 1 Open
MAJ, Contactor 1 Fail
MAJ, Major Communication Fail
MAJ, High Battery Current Shutdown
MAJ, Shorted Cell Detected
MAJ, Imminent Low V Shutdown
MAJ, Open String
MIN, Rectifier Fail
MIN, AC Fail
MIN, Thermal Probe Fail
Page 166
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
x
x
x
x
Related Commands
sta
cha
ope
x
x
x
x
x
x
x
type
range of values
text
Up to 20 characters:""
text
Up to 20 characters:""
type
range of values
number 15-50: 20 Hz
number 65-100: 100V
number 0: disable, 1: enable
number dd.d VA

Advertisement

Table of Contents
loading

Table of Contents