Alarm History
BD History
Boost History
Rectifier History
Local Port History
Modem Port History
PIN History
Network Port History

Configuration

This area of the menu system is where system operational parameters, system device information, and
alarm thresholds are set up. These items have been pre-configured for the standard QS841A controller.
Note: The controller requires time to update sectors in its flash memory when changes are made.
Please allow approximately 2 minutes for the controller to accept and place the modifications in
non-volatile memory before removing power to the unit.
Float Settings
Set the system float voltage and the thresholds for the following alarms:
Set Point
Very High Voltage Major
High Voltage Minor
BD
(Battery on Discharge) Major
Very Low Voltage Major
Page 111
© Copyright 2021 ABB. All rights reserved.
Chronological view of the last 256 alarms and events that have occurred since the last time the
history log was cleared.
Chronological view of the last 16 battery on discharge (BD) events since the last time the
history log was cleared.
Chronological view of the last 16 times the system entered boost mode since the last time the
history log was cleared.
Chronological view of the last 256 rectifier alarms and events that have occurred since the last
time the history log was cleared.
Chronological view of the last local terminal logins that have occurred since the last time the
history log was cleared. The number of these events counts towards the total number of
Modem, Network, PIN, and Local port events which can be up to 48 events.
Chronological view of the last Modem port logins that have occurred since the last time the
history log was cleared. The number of these events counts towards the total number of
Modem, Network, PIN, and Local port events which can be up to 48 events.
Chronological view of the last Front Panel access that required password entry. The number of
these events counts towards the total number of Modem, Network, PIN, and Local port events
which can be up to 48 events.
Chronological view of the last Network access events that have occurred since the last time the
history log was cleared. The number of these events counts towards the total number of
Modem, Network, PIN, and Local port events which can be up to 48 events.
System Float Voltage set-point adjustable from -42.0 to -56.5V with a factory default of -54.5V.
Alarm occurs and the unit is shut down when the system detects voltage above its set
threshold. The threshold can be set from - 50V to- 60V in 1V increments. The factory default
setting is - 57V.
Alarm indicates an abnormally high output voltage but does not shut the unit down. The alarm
threshold can be set from -50V to - 60V in 1V increments. The factory default setting is -56V.
Alarm occurs when the system is operating either completely or partially on battery power. The
alarm threshold can be set from - 46V to -55V in 0.1V increments. The factory default setting
is - 51.0V.
Alarm indicates an imminent system shutdown due to discharging batteries or low output
voltage. The alarm threshold can be set from -40V to -51V in 0.1V increments. The factory
default setting is -46.0V.