Alarm /
Description
Event
A High Voltage
threshold during the
Boost mode of
operation used to
High Boost
indicate a possible
Voltage
damaging high output
Major
DC voltage level is
present. The controller
quits the Boost mode
of operation.
A high voltage
threshold during the
Boost mode of
operation used to
High Boost
indicate an abnormally
Voltage
high output DC voltage
Minor
level is present. The
controller does not
quit the Boost mode of
operation.
A possible damaging
Very High DC bus
voltage threshold set
for the normal Float
High Float
mode of operation has
Voltage
been reached. The
Major
controller will issue a
command to shut any
offending rectifier/s
off.
Voltage threshold
during the normal
Float mode of
operation used to
High Float
indicate an abnormally
Voltage
high output DC voltage
Minor
level is present. The
controller does not
issue commands to
shut rectifier/s down.
Alarm asserted when
the DC buss voltages
reach the lower
disconnect threshold
of the two contactors.
Imminent
The controller will
LVBD
assert this alarm to
Shutdown
indicate the batteries
will be disconnected
from the load in 15
seconds. This alarm
must be enabled.
Page 184
© Copyright 2021 ABB. All rights reserved.
Default
Range /
PMJ
Setting
Severity
57V
50-60V
56V
50-60V
50-60V
57.0V
Major/
Major
Minor/
RO
50-60V
56.0V
Major/
Minor
Minor/
RO
Enabled/
Disabled
Disabled
(Major/
/ Major
Minor/
RO)
Alarm Relays
PMN
Relay 1
Relay 2
Relay 3
LED
PMJ
PMN
NORM
Relay 4
Red
Yellow
Green
LED
AUX
MD
Red