ABB CPS6000 Product Manual page 160

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Alarm Thresholds/Relays
obj,attr
description
macf1,sev
Multiple AC fail severity
mcm1,acc
Major communication relay
mcm1,ast
Major communication alarm state
mcm1,sev
Major communication severity
mrfa1,acc
Multiple rectifier fail relay
mrfa1,ast
Multiple rectifier fail alarm state
mrfa1,sev
Multiple rectifier fail severity
osa1,acc
Open string alarm relay
osa1,ast
Open string alarm state
osa1,sev
Open string alarm severity
rfa1,acc
Rectifier fail relay
rfa1,ast
Rectifier fail alarm state
rfa1,sev
Rectifier fail severity
rls1,acc
Rectifier redundancy loss relay
rls1,ast
Rect redundancy loss alarm state
rls1,sev
Rect redundancy loss severity
scd1,acc
Battery voltage imbalance relay
scd1,ast
Battery voltage imbalance alarm
state
scd1,sev
Battery voltage imbalance severity
tpa1,acc
Thermal probe fail relay
tpa1,ast
Thermal probe fail alarm state
tpa1,sev
Thermal probe fail severity
vmf1,acc
Voltage module fail relay
vmf1,ast
Voltage module fail alarm state
vmf1,sev
Voltage module fail severity
vsf1,acc
Sense voltage fail relay
vsf1,ast
Sense voltage fail alarm state
vsf1,sev
Sense voltage fail severity
The previous table outlines the various alarms that are available through the QS840A controller. Refer
to Alarm Relays in Appendix C for more details. The QS840A controller is provided with two severity
relays and two relays that may be assigned to any combination or all of the alarms noted above.
The controller is shipped with PMN assigned to Alarm Relay 2 and PMJ to Alarm Relay 1. Also, for each
alarm condition noted above, the factory severity is noted in bold. The user may change the severity of
configurable alarms from the factory set severity. Note that the alarms noted above may also be
assigned a severity of RO (Record Only). If so assigned, the alarm condition will be transmitted without
any PMJ or PMN severity.
The following is a brief explanation of the alarm conditions.
Battery on Discharge: The battery on discharge alarm is asserted when the controller detects the plant
bus voltage going below the Battery on Discharge thresholds set by the user.
High Voltage: The high voltage alarm is asserted when the controller detects the plant bus voltage
going above the High Voltage thresholds set by the user.
Page 160
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
type
range of values
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4," or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"