ABB CPS6000 Product Manual page 183

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Alarm /
Description
Event
Alarm asserted when
the controller can not
detect a single serially
Comm Loss
connected rectifier or
Minor
any number of thermal
probes that was
previously connected.
Controller on-board
Controller
ambient temperature
Ambient
measurement has
Temperatur
reached the configured
e High
high ambient
temperature threshold.
Controller on-board
Controller
ambient temperature
Ambient
measurement has
Temperatur
reached the configured
e Low
low ambient
temperature threshold.
Controller has power
Controller
and has failed.
Fail
Implemented in
hardware.
Controller determines
Defective
a "1-wire" probe t to be
Temp Probe
defective.
One or more rectifiers
Fan Fail
has reported a failed
fan
An input that has been
properly configured
Fuse Major
and mapped as a Fuse
Alarm Major has been
detected.
An input that has been
properly configured
Fuse Minor
and mapped as a Fuse
Alarm Minor has been
detected.
Alarm asserted when
the controller detects
battery temperatures
in excess of the
High Battery
configured threshold.
Temperature
Enabled with 1-wire
temperature probes
for slope thermal
compensation.
Page 183
© Copyright 2021 ABB. All rights reserved.
Default
Range /
PMJ
PMN
Setting
Severity
Major/
Minor
Minor/
RO
35-75 °C
75°C
Major/
Minor
Minor/
RO
-40-10 °C
-40°C
Major/
Minor
Minor/
RO
N/A
N/A
Major/
Minor
Minor/
RO
Major/
Major
Minor/
RO
Major/
Major
Minor/
RO
Major/
Minor
Minor/
RO
30-85 °C
55 °C
Major/
Minor
Minor/
RO
Alarm Relays
Relay 1
Relay 2
Relay 3
Relay 4
LED
LED
AUX
PMJ
PMN
NORM
MD
Red
Yellow
Green
Red

Advertisement

Table of Contents
loading

Table of Contents