ABB CPS6000 Product Manual page 164

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Serial Ports
obj,attr
Description
mp1,bdr
Modem baud rate
mp1,ins
Modem initialization string
Modem number of rings before
mp1,nrg
answering
mp1,hsh
Modem handshaking
lp1,bdr
Local RS-232 baud rate
lp1,hsh
Local RS-232 handshaking
Boost Management
obj,attr
description
bs1,abe
Auto boost enable
bs1,tmd
Max boost duration in hours
Auto Boost Enable: Activates the Auto-Boost function.
Battery Contactor
obj,attr
description
Low voltage battery disconnect
threshold
cn1,rth
Low voltage battery reconnect threshold
cn2,dth
Low voltage load disconnect threshold
cn2,rth
Low voltage load reconnect threshold
Low Voltage Battery Disconnect Threshold: Sets the voltage at which the battery contactor
disconnects the battery strings from the load.
Low Voltage Battery Reconnect Threshold: Sets the voltage at which the battery contactor reconnects
the battery strings to the system bus voltage.
Low Voltage Load Disconnect Threshold: Sets the voltage at which the battery contactor disconnects
the battery strings from the load.
Low Voltage Load Reconnect Threshold: Sets the voltage at which the battery contactor reconnects
the battery strings to the system bus voltage.
The load disconnect feature is only supported in the Distribution Module with the LVD contactor.
Page 164
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
x
x
x
x
x
x
x
x
x
x
x
x
Related Commands
sta
cha
ope
x
x
x
x
Related Commands
sta
cha
ope
x
x
x
x
x
x
x
x
type
range of values
text
2400,4800,9600,19200
Up to 20 characters:
text
"AT&FEV&C1S0=0H"
number 1-9 rings
"NO": none "SW": xon and
text
xoff
"AUTO",2400,4800,9600,1
text
92 00
"NO": none "SW": xon and
text
xoff "HW": cts and rts
type
range of values
number 0: disable, 1: enable
number 1-80:5
type
range of values
number 39-48, 42 V
number 39-48, 44 V
number 39-48, 42 V
number 39-48, 44 V

Advertisement