ABB CPS6000 Product Manual page 53

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

AC Connections to External AC Distribution Panel
CAUTION: Disconnect all AC branch circuits prior to making AC connections to the CPS6000 System.
Ensure ac power is OFF to the CPS6000 system before continuing with ac When connecting to utility
source, ensure all local and national wiring rules are being complied with.
Refer to Rectifier AC Input Current table for input current values of rectifiers
AC termination Panel
Refer to Rectifier AC Input Current table for input current values of rectifiers.
Page 53
© Copyright 2021 ABB. All rights reserved.
10 Gauge Wire
20A Circuit Breaker or
Fuse at the AC Supply
AC Duct
Figure 5-13: AC Input Connections
AC for
AC for
Bottom
Top
Shelf
Shelf
1– Inch Conduit
per Shelf
DC Bus Links
-48V
RNT

Advertisement

Table of Contents
loading