ABB CPS6000 Product Manual page 93

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

System Info: Various high level system statuses.
Controller Info
Date
Time
Ambient Temperature
Control/Operations
The following are the system control and operation functions that can be performed from the front
panel. These operations are generally used in post installation and maintenance modes.
Start Lamp Test
Restart Rectifiers
Clear Events
Uninstall Equipment
Alarm Test
Start Battery Test
Start Boost
Clear History: This area of the menus system can be used to clear of Alarm, BD and Boost History logs.
Clear Statistics: This operation allows the user to clear the Basic statistical data kept on Plant Load,
the highest battery temperature, and ambient controller temperature.
Disconnects: Allows manual disconnect and reconnect of each of the four disconnects (LVBD, LVLD1-3).
Load Factory Defaults: Initiating this operation loads all factory configured defaults back into the
controller.
History
This area of the menu system contains history information. The controller works on a first record in
first record out once the record size of a specific field is reached. The following system history logs are
available:
Alarm History
BD History
Boost History
Page 93
© Copyright 2021 ABB. All rights reserved.
Provides the versions of software for the overall controller (QS840A_MC1), boot block of the
controller, display, and the defaults.
System controller present date using configured format.
System controller present time using configured format.
System controller present temperature using configured format.
Temporarily illuminates all status indicators of attached rectifiers,
distribution monitoring and control modules and the system controller.
Restarts all system serial controlled rectifiers. Does not affect rectifiers, and other system
devices that are already functioning.
Used to clear momentary events or alarms. It clears the following system alarms: Check
Battery, Reserve Time Low, Battery Voltage Imbalance
Clears alarms related to the removal of a system component such
as a rectifier, thermal probe, or voltage monitoring module.
Initiates the asserting the Form-C alarms.
Initiates the manual battery test feature. A stop battery test operation is displayed to
interrupt the testing and return the unit to normal operation. The manual battery test utilizes
the configured test duration and a system bus voltage threshold to represent the end of
reserve.
Initiates the manual battery Boost feature. A stop battery Boost operation is displayed to
interrupt the Boost operation mode and return the unit to normal operation.
Chronological view of the last 30 alarms and events that have occurred since the last time the
history log was cleared.
Chronological view of the last 10 battery on discharge (BD) events since the last time the
history log was cleared.
Chronological view of the last 10 times the system entered boost mode since the last time the
history log was cleared.