Specifications

Shelf
Power Slots per Shelf
Power Units
5
Installed Position
Rectifier Input Distribution
System Architecture
Primary Power Bus Current
with Bulk Output Module
Output Distribution
Maximum Discharge Current
Maximum Recharge Current
Operating Ambient Temperature
Altitude
Humidity
Audible Noise
Radiated and Conducted Emissions
Harmonics
Voltage Fluctuations
Electromagnetic Immunity
Electrostatic Discharge
RF Immunity
EFT
Surge
Conducted Immunity
Voltage Dips, Interruptions, and Variations
Earthquake Rating
Safety Agency Approval
Page 15
© Copyright 2021 ABB. All rights reserved.
Installed from the Right
Bulk Output Module
Distribution Module
Ringer Chassis
Installed from the Left
Rectifiers
Primary Bus
Bulk Output Module
Single-Slot and Double-Slot
Distribution Modules
Table 2-A: CPS6000 System Specifications
Single 19-inch or 23-inch shelf
4 (19-inch shelf), 5 (23-inch shelf)
Unit
Bulk Output Module
Single-Slot Distribution Module
Double-Slot Distribution Module
Ringer Chassis
Rectifiers
(19-inch shelf)
(23-inch shelf)
Dual ac input (19 and 23-inch shelves)
Individual ac input (19 and 23-inch shelves) Single ac input (19
and 23-inch shelves)
Primary output: 1 primary output power bus per shelf
19-inch shelf: 227A
23-inch shelf: 283A
Battery connections: double-hole lugs to terminate battery
strings.
-48 V
bulk power outputs to loads or distribution
dc
Bullet-style circuit breakers
GMT-style fuses
See Note 2.
Based on rectifier capacity. See Note 2
Installed shelf –48V rectifier capacity minus plant –48V load
-40 to 75 °C (-40 to 167 °F), see Note 3
-200 to 13,000 feet (-61 to 3962 meters). See Note 4
10% to 95% non-condensing
< 60 dBA
FCC Part 15, Class B
EN55022 (CISPR22), Class B
EN61000-3-2 (IEC61000-3-2)
EN61000-3-3 (IEC61000-3-3)
Meets Telcordia GR-1089-CORE
EN61000-4-2 Level 3
IEC61000-4-3 Level 3, 10 V/m
IEC61000-4-4 Level 3, No Error; Level 4, No Damage
IEC 61000-4-5 Level 3, No Error; Level 4, No Damage
IEC 61000-4-6 Level 3, 10V
IEC 61000-4-11
Zone 4, upper floors
Underwriters Laboratories (UL) Listed per Subject Letter
1801: Power
Distribution
Equipment, and
cUL Certified (CSA 22.2 950): Safety of
Information Technology Equipment
VDE licensed to VDE0805/EN60950
Max. per
Power Slots
Shelf
Each
1
0
1
1
1
2
2
1
4
1
5
1
Center