Table 5. SPCN Error Codes for I/O Subsystems (continued)
Error Code Description
1nn1 1527 Power supply 2 thermal fault
1nn1 1B01 +12V load fault
1nn1 1B02 +5V load fault
1nn1 1B03 +3.3V load fault
1nn1 1B04 -12 load fault
1nn1 2600 Power good fault
1nn1 2603 Power domain fault
1nn1 2605 Power good 1.8 V fault
Action/
Possible Failing FRU
1. Check for obstructions to the air flow
around the I/O subsystem.
2. I/O subsystem power supply 2,
Location: U0.dd-V2
3. I/O subsystem backplane,
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
1. I/O subsystem power supply 1
Location: U0.dd-V1
2. If power supply 2 is present, use removed
power supply 1 to replace power supply 2.
3. I/O subsystem backplane
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
1. Replace power supply 1,
Location: U0.dd-V1
2. If power supply 2 is present, use removed
power supply 1 to replace power supply 2.
3. I/O subsystem backplane
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
1. Replace power supply 1,
Location: U0.dd-V1
2. If power supply 2 is present, use removed
power supply 1 to replace power supply 2.
3. I/O subsystem backplane
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
1. Replace power supply 1,
Location: U0.dd-V1
2. If power supply 2 is present, use removed
power supply 1 to replace power supply 2.
3. I/O subsystem backplane
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
I/O subsystem backplane,
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
I/O subsystem backplane,
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
I/O subsystem backplane,
Location: U0.dd-P1
See the notices on page 255 for "dd" values.
Chapter 5. Error Code to FRU Index