Calibration - Indoor Sensor
The C7189U1005 Wall Mount Temperature Sensor is
calibrated at the factory and cannot be recalibrated in the
field.
Table 12. C7189U1005 Sensor Resistance at
Room Temperature.
Room
Temperature
Ohms of
°F
°C
Resistance
40
4.4
22537
42
5.6
21516
44
6.7
20546
46
7.8
19626
48
8.9
18754
50
10.0
17926
52
11.1
17136
54
12.2
16387
56
13.3
15675
58
14.4
14999
60
15.6
14356
62
16.7
13743
64
17.8
13161
66
18.9
12607
68
20.0
12081
70
21.1
11578

BACKUP CONTROL

This section explains when backup control is used. For
example, if batteries in the wireless indoor sensors are
depleted.
If the Thermostat is Part of the
Temperature Average
1. The thermostat controls the system using the
remaining sensors that are part of the temperature
average.
2. If there are no remote indoor sensors remaining, the
thermostat controls the system using its internal
sensor.
3. If the internal thermostat sensor is not available and
a Return Air Sensor is connected, the Backup Control
in the EIM is used. The backup control maintains 55
°F in heat, 85 °F in cool and operates the fan continu-
ously to sense and control temperature.
Room
Temperature
Ohms of
°F
°C
Resistance
72
22.2
11100
74
23.3
10644
76
24.4
10210
78
25.6
9795
80
26.7
9398
82
27.8
9020
84
28.9
8659
86
30.0
8315
88
31.1
7986
90
32.2
7672
92
33.3
7372
94
34.4
7086
96
35.6
6813
98
36.7
6551
100
37.8
6301
®
THX9321 PRESTIGE
2.0 AND THX9421 PRESTIGE
If the Thermostat is NOT Part of the
Temperature Average
1. The thermostat controls the system using the
remaining sensors that are part of the temperature
average.
2. If there are no remote indoor sensors remaining and
a Return Air Sensor is connected, the Backup Control
in the EIM is used. The backup control maintains 55
°F in heat, 85 °F in cool and operates the fan continu-
ously to sense and control temperature.

REPLACING A THERMOSTAT

When you replace a thermostat, you must reset the
RedLINK accessories before connecting them to the new
thermostat.
Follow the instructions below:
At the Equipment Interface Module (EIM)
1. Press and hold the CONNECT button on the EIM until
the CONNECTED LED glows amber (hold for about
10 seconds).
2. Follow the prompts on the screen to connect the new
thermostat to the EIM. See page 10.
At the Portable Comfort Control
1. Press and hold the blank space (or arrow) in the lower
right hand corner of the screen until the display
changes (hold for about 4 seconds).
2. Press REMOVE, then YES to disconnect from the old
thermostats.
3. To reconnect the thermostat, go to "Linking
RedLINK™ Accessories" beginning on page 16.
At the Indoor Sensor, RedLINK Internet
Gateway, Entry/Exit Remote, Vent-Filter
Boost Remote or TrueSTEAM Wireless
Adapter
1. Press and hold the CONNECT button on the acces-
sory until the status light glows amber (hold for about
10 seconds).
2. To reconnect the thermostat, go to "Linking
RedLINK™ Accessories" beginning on page 16.
133
®
IAQ WITH EIM
Press and hold
the blank space
(or arrow may be
present)
Fig. 321.
68-0311—08