Control functions
9.1.6
988
Signals
Table 962:
CBXCBR Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
TRIP
BOOLEAN
SYNC_OK
BOOLEAN
SYNC_ITL_BYP
BOOLEAN
1) Not available for monitoring
2) Always direct operation
Table 963:
DCXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
1) Not available for monitoring
2) Always direct operation
Table 964:
ESXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
Table continues on next page
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
1)2)
Auxiliary open
0=False
1)2)
Auxiliary close
0=False
Trip signal
1=True
Synchronism-check OK
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Default
Description
0=False
Apparatus open position
0=False
Apparatus close position
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Executes the command for open direction
0=False
Executes the command for close direction
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Default
Description
0=False
Apparatus open position
0=False
Apparatus close position
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
1MRS757644 F
1)
1)
1)2)
1)2)