ABB RELION 620 Series Technical Manual page 999

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757644 F
9.2
9.2.1
9.2.2
9.2.3
620 series
Technical Manual
Table 979:
ESXSWI Technical revision history
Technical revision
B
C
Disconnector position indication DCSXSWI and
Earthing switch indication ESSXSWI
Identification
Function description
Disconnector position indication
Earthing switch indication
Function block
A071280 V2 EN
Figure 511:
Function block
A071282 V2 EN
Figure 512:
Function block
Functionality
The functions DCSXSWI and ESSXSWI indicate remotely and locally the open,
close and undefined states of the disconnector and earthing switch. The functionality
of both is identical, but each one is allocated for a specific purpose visible in the
function names. For example, the status indication of disconnectors or circuit breaker
truck can be monitored with the DCSXSWI function.
The functions are designed according to the IEC 61850-7-4 standard with the logical
node XSWI.
Change
Maximum and default values changed to 60 s and
10 s respectively for
value changed to 30 s for
setting.
Outputs OPENPOS and CLOSEPOS are forced to
"FALSE" in case status is Faulty (11).
IEC 61850
IEC 60617
identification
identification
DCSXSWI
I<->O DC
ESSXSWI
I<->O ES
Section 9
Control functions
Event delay settings. Default
Operation timeout
ANSI/IEEE C37.2
device number
I<->O DC
I<->O ES
993