Section 9
Control functions
9.1.7
Table 968:
CBXCBR Non group settings (Basic)
Parameter
Operation
Select timeout
Pulse length
Control model
Operation timeout
Identification
Table 969:
CBXCBR Non group settings (Advanced)
Parameter
Operation counter
Adaptive pulse
Event delay
Vendor
Serial number
Model
Table 970:
DCXSWI Non group settings (Basic)
Parameter
Operation
Select timeout
Pulse length
Table continues on next page
990
Name
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
Settings
Values (Range)
Unit
1=on
5=off
10000...300000
ms
10...60000
ms
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
10...60000
ms
Values (Range)
Unit
0...10000
0=False
1=True
0...10000
ms
Values (Range)
Unit
1=on
5=off
10000...300000
ms
10...60000
ms
Type
Description
BOOLEAN
Apparatus closed position
BOOLEAN
Apparatus position is ok
BOOLEAN
Opening is enabled based on the input status
BOOLEAN
Closing is enabled based on the input status
Step
Default
1=on
10000
30000
1
200
4=sbo-with-
enhanced-security
1
500
CBXCBR1 switch
position
Step
Default
1
0
1=True
1
200
0
0
0
Step
Default
1=on
10000
30000
1
100
1MRS757644 F
Description
Operation mode on/off
Select timeout in ms
Open and close pulse length
Select control model
Timeout for negative termination
Control Object identification
Description
Breaker operation cycles
Stop in right position
Event delay of the intermediate position
External equipment vendor
External equipment serial number
External equipment model
Description
Operation mode on/off
Select timeout in ms
Open and close pulse length
Technical Manual
620 series