Uploading a PLC project from the control system
You can back up a PLC project from the permanent memory of the control system using PLC Programming Tool, a USB
memory stick, or the network drive.
To upload a PLC project using PLC Programming Tool, proceed as follows:
Commissioning Manual
6FC5397-4EP10-0BA8, 07/2018
1.
Establish the communication between the control system and PLC Programming Tool. For
more information, see Section "Connecting with PLC Programming Tool (Page 42)".
2.
Select from the main screen menu as follows or click the toolbar button
and empty PLC project:
3.
Select from the main screen menu as follows or click the toolbar button
load:
4.
Click this button to proceed directly. You can also select the checkbox for data blocks to
include the actual values of the data blocks, and then click this button.
5.
The upload has been completed when the following message appears.
to create a new
to start the up-
189