Drive
side
1. Strip the specified length (see below) of the outer sheath at the end of the cable.
4 x 2.5 mm
4 x 10 mm
2. Keep the exposed braided shield as long as 25 mm (± 5 mm) and cut off the rest of the shield. Fold the
braided shield backwards.
3. Pass the cable through a heat-shrinkable tube. Heat the tube until it shrinks to wrap tightly around the ca-
ble.
4. Strip the inner sheath without damage to the insulation of each cable conductor.
5. Pass white cable marker tubes through corresponding cable conductors.
6. Strip 10 mm of the insulation at the end of each cable conductor.
7. Insert cable wires into individual conductor terminals. Use a crimping tool to crimp the terminals (minimum
tensile strength: 350 N).
8. (This step is necessary only for 4 x 10 mm
mm
/4 x 4 mm
2
completely cover the bending area of the terminal. Heat the tube until it shrinks to wrap tightly around the
terminal.
9. Use a hose clamp to secure the power cable to the drive.
For more information about the connectors and hose clamps, such as recommended suppliers and article numbers, see
Section "Cables and connectors (Page 29)".
458
/4 x 4 mm
power cable: 100 mm
2
2
/4 x 16 mm
power cable: 110 mm
2
2
power cables.) Pass each conductor terminal through a heat-shrinkable tube, which must
2
/4 x 16 mm
power cables. Skip this step if you assemble 4 x 2.5
2
2
Commissioning Manual