Fault list
Fault
F1000: Internal software
error
Reaction: OFF2
Acknowledgement: POWER
ON
F1001: Floating Point excep-
tion
Reaction: OFF2
Acknowledgement: POWER
ON
F1002: Internal software
error
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F1003: Acknowledgement
delay when accessing the
memory
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F1015: Internal software
error
Reaction: OFF2
Acknowledgement: POWER
ON
F1018: Booting has been
interrupted several times
Reaction: NONE
Acknowledgement: POWER
ON
F1030: Sign-of-life failure for
master control
Reaction: OFF3
Acknowledgement:
IMMEDIATELY
F1611: SI CU: Defect de-
tected
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
464
Cause
An internal software error has occurred.
An exception occurred during an operation
with the Floating Point data type.
An internal software error has occurred.
A memory area was accessed that does
not return a "READY".
An internal software error has occurred.
Module booting was interrupted several
times. As a consequence, the module
boots with the factory setting.
Possible reasons for booting being inter-
rupted:
Power supply interrupted.
•
CPU crashed.
•
Parameterization invalid.
•
After this fault is output, then the module is
booted with the factory settings.
For active PC master control, no sign-of-
life was received within the monitoring
time.
The drive-integrated "Safety Integrated"
(SI) function on the Control Unit (CU) has
detected an error and initiated an STO
Remedy
Evaluate fault buffer.
•
Carry out a POWER ON (power off/on) for
•
all components.
Upgrade firmware to later version.
•
Contact the Hotline.
•
Replace the Control Unit.
•
Carry out a POWER ON (power off/on) for
•
all components.
Upgrade firmware to later version.
•
Contact the Hotline.
•
Carry out a POWER ON (power off/on) for
•
all components.
Upgrade firmware to the latest version.
•
Contact the Hotline.
•
Carry out a POWER ON (power off/on) for
•
all components.
Contact the Hotline.
•
Carry out a POWER ON (power off/on) for
•
all components.
Upgrade firmware to the latest version.
•
Contact the Hotline.
•
Carry out a POWER ON (power off/on).
•
After switching on, the module reboots from
the valid parameterization (if available).
Restore the valid parameterization.
•
Examples:
Carry out a first commissioning, save, carry
•
out a POWER ON (switch-off/switch-on).
Load another valid parameter backup (e.g.
•
from the memory card), save, carry out a
POWER ON (switch-off/switch-on).
Note:
If the fault situation is repeated, then this fault
is again output after several interrupted boots.
Contact the Hotline.
Make sure that the high level duration of
•
the inut pulse is larger than 500 ms.
Carry out a POWER ON (power off/on) for
•
all components.
Upgrade software.
•
Replace the Control Unit.
•
6FC5397-4EP10-0BA8, 07/2018
Commissioning Manual