Setting Drive Bus address

When connecting the SINAMICS V70 to the SINUMERIK 808D ADVANCED, you must set the Drive Bus address with the
BOP. Six addresses in total are available. You must set a proper address according to the actual application of the drive.
● 11: X axis
● 12: Y axis (or additional axis for the turning variant of the control system)
● 13: Z axis
● 14: Digital spindle (SINAMICS V70 spindle drive only)
● 15: Additional axis 1 *
● 16: Additional axis 2 *
* Note that Drive Bus addresses 15 and 16 are not supported on the control system with PPU15x.3. In addition, to use Drive
Bus address 16, the drive firmware version must be 1.05.00.02 or higher.
To set Drive Bus address with the BOP, proceed as follows.
Note
After setting a proper address, you must restart the drive to apply your setting.
For more information, see Section "Configuring Drive Bus addresses (Page 118)".
A.1.5.2

Jog

To run the connected motor with the Jog function and view the Jog speed or Jog torque, proceed as follows:
For more information, see Section "Jog test (Page 116)".
Commissioning Manual
6FC5397-4EP10-0BA8, 07/2018