PRE-INSTALLATION

NOTES:
1. The maximum distance from the RPM to the PAL -1 is 6 feet. The two modules must be in the same room.
2. For NFPA 72 Local, Auxiliary and Remote Station configurations, connect the output of the RPM to any
UL EDP listed printer.
3. The printer must support the EPSON FX command set.
4. For NFPA 72 Proprietary of UL 1076 configurations use printer SIEMENS Model PAL-1, a UL listed for fire Centronics parallel printer.
5. The printer is supervised for AC loss, off line, paper out, paper jam, and connection to the RPM.
6. After loading the paper in the PAL-1 printer, turn off the power and follow the steps below.
• While pressing the LOAD PARK button, turn on the power to the PAL -1 printer. Keep pressing the LOAD PARK button for 5 seconds.
• Release the LOAD PARK button.
• The current setting will print.
• When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON LINE button.
Figure 4
Connecting The Printer To The RPM
Siemens Industry, Inc.
Building Technologies Division
Before connecting either the printer, power, FSI or the HNET, the network address
must be set for the RPM using the three-position switch. (Refer to Figure 2 for the
location of the switch.) The address for the RPM must be the same as the address
selected for it in the Zeus Programming Tool. To increment each digit of the address,
press the "+" button above the desired digit; to decrement each digit, press the "-"
button below the desired digit. The range of allowable addresses is from 001 to
251 (leading zeros must be used).
If the RPM is located at the end of the HNET network (Style 4 only), the termination
switch must be set to ON. Otherwise it must be set to OFF .
Figure 3
Installing The RPM Terminal Block Covers
Two terminal block covers are provided with the RPM. Each comes as two separate
parts, a lower bracket which has a ¾ inch conduit opening and a cover. Attach the
lower bracket to each end of the RPM using four of the #10 nuts provided in the
RPM hardware kit. Reserve the covers and the remaining hardware until the RPM is
mounted and wired.
Mount the RPM to either the wall or desk where the PAL -1 is located. Use the four
mounting holes in the lower bracket.
PAL-1 or EDP LISTED PRINTER
120 VAC
60 Hz.
CABLE SUPPLIED WITH RPM
SUPERVISED
POWER LIMITED
CENTRONICS
PARALLEL
3
RPM
P/N 315-033270-12