Fault
F7420: Drive: Current set-
point filter natural frequency
> Shannon frequency
Reaction: NONE
Acknowledgement:
IMMEDIATELY
F7450: Standstill monitoring
has responded
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7452: Following error too
high
Reaction: OFF1
Acknowledgement:
IMMEDIATELY
F7801: Motor overcurrent
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F7802: Infeed or power unit
not ready
Reaction: OFF2
Acknowledgement:
IMMEDIATELY
F7815: Power unit has been
changed
Reaction: NONE
Acknowledgement:
IMMEDIATELY
Commissioning Manual
6FC5397-4EP10-0BA8, 07/2018
Cause
One of the filter natural frequencies is
greater than the Shannon frequency
(2KHz).
Filter 1 (p1658, p1660)
Filter 2 (p1663, p1665)
Filter 3 (p1668, p1670)
Filter 4 (p1673, p1675)
After the standstill monitoring time expired,
the drive left the standstill window.
Position loop gain too low.
Position loop gain too high (instabil-
ity/oscillation).
Mechanical overload.
Connecting cable, motor/drive convert-
er incorrect (phase missing, inter-
change).
The difference between the position set-
point position actual value (following error
dynamic model) is greater than the toler-
ance.
The drive torque or accelerating capac-
ity exceeded.
Position measuring system fault.
Position control sense incorrect.
Mechanical system locked.
Excessively high traversing velocity or
excessively high position reference
value (setpoint) differences.
The permissible motor limit current was
exceeded.
Effective current limit set too low.
Current controller not correctly set.
Motor was braked with an excessively
high stall torque correction factor.
Up ramp was set too short or the load
is too high.
Short-circuit in the motor cable or
ground fault.
Motor current does not match the cur-
rent of Motor Module.
After an internal power-on command, the
infeed or drive does not signal ready be-
cause of one of the following reasons:
Monitoring time is too short.
DC link voltage is not present.
Associated infeed or drive of the sig-
naling component is defective.
The code number of the actual power unit
does not match the saved number.
Remedy
Reduce the numerator or denominator
natural frequency of the current setpoint fil-
ter involved at the control system side.
Switch out the filter involved (p1656).
Check the causes and resolve.
Check the causes and resolve.
Reduce the stall torque correction factor.
Increase the up ramp or reduce the load.
Check the motor and motor cables for
short-circuit and ground fault.
Check the Motor Module and motor combi-
nation.
Ensure that there is a DC link voltage.
Check the DC link busbar. Enable the in-
feed.
Replace the associated infeed or drive of
the signaling component.
Connect the original power unit and power up
the Control Unit again (POWER ON).
467