Parameter sets

3.7.7 Locking of parameter sets

Parameter sets, which shall not be selected, can be locked with Fr.03. If one of the locked sets is selected, the
adjusted response in Pn.18 is executed (default: set source error E.SEt) .
Fr.03: Parameter set lock
Value
1
2
4
8
16
32
64
128

3.7.8 Parameter set activation delay/ deactivation delay (Fr.05, Fr.06 )

The time is adjusted with these parameters:
- with which the activation of a new set is delayed (Fr.05)
- with which the deactivation of an old set is delayed (Fr.06)
At set changeover, the switch-off time of the old set and the switch-on time of the new set are added.
Picture 3.7.8 Activation delay and deactivation delay
Actual set
Default set
Example
on
Set
Fr.05
0
0s
1
2s
2
0s
3
2s
Page3.7 - 10
Locked set
0
1
2
3
4
5
6
7
Set3
Set2
Set1
1
Set0
Set3
Set2
Set1
Set0
off
Fr.06
0s
0s
1s
2s
COMBIVERT R6-S
Example (set 2 and 5 locked)
-
-
4
-
-
32
-
-
Sum: 36
2
3
1:
Activation delay set 3 of 2s
2:
Deactivation delay set 3 of 2s
3:
Deactivation delay set 2 of 1s +
Activation delay set 1 of 2 s
4:
immediate change-over since no delay is adjusted
5:
Deactivation delay set 2 of 1s +
Activation delay set 3 of 2s
6:
Deactivation delay set 3 of 2s
5
4