3.4.16 Invert conditions for flags 0...7 (do.08...do.15)
Picture 3.4.16 Invert and selection of the switching conditions
do.00
do.01
do.02
do.03
do.04
do.05
do.06
do.07
Each of the eight switching conditions (do.00 ... do.07) can be inverted separately for each marker with para-
meters do.08 ... do.15. Any switching condition can be used as non-condition with this function. The parameter
is bit-coded. The value for the switching condition to be inverted must be entered in do.08...do.15 according to
picture 3.4.15. If several conditions shall be inverted, the sum must be formed.
3.4.17Selection of the conditions for flags 0...7 (do.16...do.23)
Parameters do.16...do.23 serve for the selection of the 8 preassigned conditions. The selection for each flag
occurs separately, whereby it can be selected between none and up to all 8 conditions. The value for the se-
lected condition must be entered in do.16...do.23 according to picture 3.4.15. If several conditions shall be
selected, the sum must be formed.

3.4.18 AND/OR connection of the conditions (do.24)

After the switching conditions are selected for each output, now it can be determined how these are linked. As
standard all conditions are OR-linked, i.e. if one of the selected conditions is met, the flag is set. An AND opera-
tion is available as further possibility which can be adjusted with do.24. AND operation means that all selected
conditions must be met before the flag is set.
Parameter do.24 is bit-coded. The table under 3.4.19 shows the assignment.
© KEB, 2008-02
do.08...15
do.16...23
1
1
1
2
1
2
4
1
4
8
1
8
16
1
16
32
1
32
64
1
64
128
1
128
COMBIVERT R6-S
Digital in- and outputs
8
do.24
3
10
Seite 3.4 - 15