1.3.1.3 Control terminal strip X2A

PIN Function
10
24 V DC input
11
Mass
12
Digital input 1
13
Digital input 2
14
Digital input 3
15
Digital input 4
16
Digital in-/output
17
24V output
18
Mass
19
Digital output 1
20
Digital output 2
21
Analog output / gain
22
24V output
23
Mass
24
Relay 1 / NO
25
Relay 1 / NC
Relay 1 / switching
26
contact
27
Relay 2 / NO
28
Relay 2 / NC
Relay 2 / switching
29
contact
*) The relay outputs must be operated with max. 48 V DC protective separation voltage to guarantee the CE
standard. After consultation KEB a current of max. 1 A DC is permissible for 120 V AC.
© KEB, 2008-02
Core cross-section 0,14...1,5 mm², tightening torque 0,5 Nm
Name
Uin
COM
ST
I1
I2
I3
I/O (I4)
Uout
COM
O1
O2
ANOUT
Uout
COM
RLA
RLB
RLC
FLA
FLB
FLC
COMBIVERT R6-S
X2A
Description
external supply of the control board
Reference potential
Control release / Reset
programmable
programmable
programmable
Active signal (connection of all R6 at paral-
lel operation in master-slave procedure)
Voltage supply for in- and outputs
Reference potential
Transistor output (DC > CP.19)
Transistor output (error message)
Difference between actual supply frequen-
cy and set supply frequency
see terminal 17
Reference potential
Relay output
Ready signal (no error)
Relay output
(DC > CP.19 and tightened load-shunt)
Hardware
Specification
23...30 V DC / 1A
Ri: 4,4 kΩ
ca. 24 V / max.
100 mA
I
: 25 mA
max
I
: 25 mA
max
1 V pro 0,1 Hz
Difference
max. 30 V DC *)
0,01...2 A DC
max. 30 V DC *)
0,01...2 A DC
Seite 1.3 - 5