Deactivate regeneration
cS.05 Puls off delay, cS.06 puls off level (CP.32)
If the actual power (ru.81 / CP.13) exceeds the defined value in cS.06 (CP.32), the modulation is switched off
after expiration of the adjusted time in cS.05.
The setting for the respective application can be determined as follows:
-
Start-up the drive based on the default values and the adjustment via Pn.19 (CS.33).
-
Regenerative operation of the drive, e.g. deceleration process.
-
Stop the drive (LS), control release at R6 is active. R6 remains in status ‚rEGEn'.
-
Read actual power ru.81 (CP.13) and enter the value plus one offset of approx.10% in cS.06 (CP.32). R6
changes into status ‚Stb'
-
Check adjustment. R6 must always change into status ,Stb' after completion of regenerative operation.
-
Increase cS.06 (CP.32) if necessary.
© KEB, 2008-02
COMBIVERT R6-S
Start-up
Page 4.2 - 5