Digital in- and outputs
Description
To switch the digital outputs up to 8 conditions can be selected from different conditions. These are entered in
do.00...do.07. The switching condition 0 and 1 can be filtered with do.43 and do.44. Parameter ru.23 displays,
if one or several of these conditions are met. Now it can be selected for each flag, which of the 8 conditions
shall be valid for it (do.16... do.23). Each condition can be inverted before the selection (do.08... do.15). As
standard all conditions (if several are selected) are OR-linked. It can be changed into AND-linkage i.e., all se-
lected conditions for the flag must be fulfilled, in order that the flag is set. Parameter ru.24 displays the flags
set in this level. do.33 ... 40 form a second logic level, whereby a selection of flags from logic level 1 can be
made. Each flag can be inverted with do.25 ... 32. do.41 adjusts the type of the linkage (AND/OR). Parameter
do.42 serves for inverting one or several outputs. The output signals are assigned to the terminals with do.51.
ru.80 displays the digital output state, ru.25 displays the output terminal state. The internal outputs OA...OD are
directly connected with the internal inputs IA...ID.
3.4.13Output signals / hardware
Picture 7.3.13a Transistor outputs
X2A
The current of X2A.17, 19 is limited to 25mA. A protective wiring shall be provided at inductive load at the relay
outputs or transistor output (free-wheeling diode)!!
3.4.14 Output filter (do.43, do.44)
A filter can be set for switching condition 0 with do.43. For switching condition 1 with do.44. The change of a
switching condition must be applied for the filter time, then it becomes active at the output of the filter. If the
change is cancelled during filter time, the filter time is reset and restart at the next change. The filter time can
be adjusted in a range of 0 (off)...1000ms.
Seite 3.4 - 12
Picture 7.3.13b Relay outputs
+24V / 50mA
O1
O2
Uout
COM
X2A
19
20
17
23
COMBIVERT R6-S
R1
RLA
RLB
RLC
24
25
26
max. 30V / 0,01...2A
R2
FLA
FLB
FLC
X2A
27
28
29
max. 30V / 0,01...2A
© KEB, 2008-02