Parameter
SY.42
Status word high
The current condition of the COMBIVERT can be readout with the status word. The status word long
(SY.44) consists of the two 16 bit parameters status word high (SY.42) and status word low (SY.51). The
status word is bit-coded.
Bit
Value
1: I1
2: I2
4: I3
8: I4
0..7
16: IA
32: IB
64: IC
128: Id
256: O1
512: O2
1024: R1
2048: R2
8..15
4096: OA
8192: OB
16384: OC
32768: OD
Parameter
SY.43
Control word long
The control word is used for status control of the inverter via bus. The control word long (SY.43) consists of
the two 16 bit parameters control word high (SY.41) and control word low (SY.50). The status word is bit-
coded.
Parameter
SY.44
Status word long
The current condition of the COMBIVERT can be readout with the status word. The status word long
(SY.44) consists of the two 16 bit parameters status word high (SY.42) and status word low (SY.51). The
status word is bit-coded.
© KEB, 2008-02
COMBIVERT R6-S
Operating and appliance data
Addr.
R
002Ah
ro
Description
Display of the internal input terminal status (input terminals and software inputs after
the input processing block). Corresponds to the display in ru.22 „internal input state"
Display of the state of the output terminals and the software outputs (digital outputs
after the output processing block). Corresponds to the display in ru.25 „output termi-
nal state"
Addr.
R
PG E
002Bh KB
Addr.
R
PG E
002Ch
ro
PG E
Min. value
Max. value
-
-
0
Min. value
Max. value
-
+
-2147483648 2147483647
Min. value
Max. value
-
-
-2147483648 2147483647
Res.
[?]
65535
1
-
Res.
[?]
Default
1
-
Res.
[?]
1
-
Page 3.2 - 17
Default
0
3
0
10
Default
0