3.4.21 AND / OR connection of the flags (do.41)
After the flags are selected for each output, the linkage type can be determined now. As standard all flags are
OR-linked, i.e. the output switches, if one of the selected flags is set. An AND linkage is available as further
possibility which can be adjusted with do.41. AND linkage means, all selected flags must be set before the
output switches.
Picture 3.4.21a. Linking the outputs
do.33
do.34
do.40
As shown in picture 3.4.22b. the outputs can be inverted again with parameter do.42 after linking. The parame-
ter is bit-coded, i.e. in accordance with the following table the associated value to the output must be entered.
If several outputs shall be inverted, the sum must be formed.
Picture 3.4.21b. Invert the outputs
do.41
© KEB, 2008-02
do.41
8
&
0
Bit 0
O1
>
1
1
8
&
Bit 1
0
O2
>
1
1
8
&
Bit 7
0
OD
>
1
1
do.42
1
1
Bit 0
2
1
Bit 1
4
1
Bit 2
8
1
Bit 3
16
1
Bit 4
32
1
Bit 5
64
1
Bit 6
128
1
Bit 7
COMBIVERT R6-S
Digital in- and outputs
3
10
Seite 3.4 - 17