Protective functions

3.6.1.7 Bus error

The COMBIVERT contains two watchdogs that monitor the communication between an external bus, the ope-
rator, and the inverter control.
With parameter Pn.05 „Response to E.bus", the response to a watchdog error is defined. Dependent on the
chosen adjustment, either „Error! Watchdog" (E.buS) or „Warning! Watchdog error" (A.buS), is issued or a war-
ning message via a digital output is generated.
Watchdog-time (Pn.06)
This watchdog monitors the communication at the operator interface. With an activated watchdog, the response
set under Pn.05 is triggered after expiration of an adjustable time (0.01...40 s) without received telegrams.
By input of the value „0: off" the function is deactivated.
HSP5 Watchdog-time (SY.09)
The HSP5 watchdog function monitors the communication of the HSP5 interface (control card - operator; or
control card - PC). The adjusted response in Pn.05 is released if no telegrams after expiration of an adjustable
time (0.01...10 s) are received. Value „0: off" deactivates the function.

3.6.1.8 Set selection error

Sets can be locked with Fr.03 „Parameter set lock". If a disabled set is selected, the inverter remains in the old
set, i.e., no set change occurs.
The response to the selection of a locked set is defined via Pn.18 „E.Set stopping mode". In the factory setting,
the error „39: Error! Parameter set selection" (E.Set) is triggered. For Pn.18 = 1...5 a malfunction „102: Warning!
Set selection error" (A.Set) is generated. For Pn.18 = „6: Function disabled", the drive continues running in the
old set without message.

3.6.1.9 Hardware error

On some inverter types monitorings for the internal hardware (e.g., switch-mode power supply or loading shunt
relay) are integrated. If one of these monitoring circuits reports an error, „12: general power circuit error" (E.
PU) is triggered.
Error Messages
Error! EEPROM
E.EEP
defective
E.LSF
Error ! load shunt fault
Error ! power circuit
E.Puci
unknown
Error ! power unit
E.Puch
changed
Error ! power circuit
E.PUIN
coding
Seite 3.6 - 6
After reset the operation is again possible (without storage in the
21
EEPROM).
Error: Load-shunt relay has not picked up, occurs for a short time during
the switch-on phase, but must automatically be reset immediately. If
the error message remains the following causes may be applicable:
15
-
-
-
During the initialization the power circuit could not be recognized or
49
was identified as invalid.
Power circuit identification was changed; with a valid power circuit this
error can be reset by writing to SY.3. If the value displayed in SY.03 is
50
written, only the power-circuit dependent parameters are reinitialized.
If any other value is written, then the default set is loaded. On some
systems after writing Sy.03 a Power-On-Reset is necessary.
Error: Software version for power circuit and control card are different.
14
Error cannot be reset.
COMBIVERT R6-S
load-shunt defective
input voltage wrong or too low
high losses in the supply cable
© KEB, 2008-02