3.7 Parameter sets
KEB COMBIVERT includes eight parameter sets (0...7), i.e., all programmable parameters are eight times
available in the inverter and can be assigned independently with different values. Since many parameters in
the parameter sets have the same values, it would be complicated to adjust each parameter individually in each
set. This section describes how to copy, lock and select entire parameter sets and to reinitialize the inverter.
3.7.1 Not set-programmable parameters
Certain parameters are not set-programmable, since their value must be the same in all sets (e.g. bus address
or baud rate). The parameter set number is missing in the parameter identification in order that these parame-
ters are immediately visible.
Always the same value is valid for all non set-programmable parameters independent of the selected
parameter set!
The following parameters are not set-programmable:
SY-Parameter
ru-Parameter
di-Parameter
In-Parameter (exception: In.24 and 25)
Pn.00...19
3.7.2 Security parameters
The security parameters include the baud rate, inverter address, hour counter, control type, serial number/cu-
stomer number, trimming values, and fault diagnosis. It make sense that they are not overwritten when loading
the default set.
SY.02/ 03/ 06/ 07/ 11
ru.40/ 41
ud.01
Fr.01
In.10...16/ 24...30
3.7.3 Indirect and direct set-addressing
The parameter values are displayed and edited at indirect set-addressing, which of the set pointer (Fr.09) is
adjusted. Direct set-addressing allows the display or writing of a parameter value directly into one or more pa-
rameter sets independent of the set pointer. Direct set programming is only possible via bus operation.
© KEB, 2008-02
COMBIVERT R6-S
Parameter sets
ud.01...17
Fr.02...04/ 07/ 09/ 11
An.41...52
LE.17-26
3
10
Page3.7 - 3