KEB COMBIVERT R6-S Series Instruction Manual

KEB COMBIVERT R6-S Series Instruction Manual

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6-S Series:
Table of Contents

Advertisement

Quick Links

C O M B I V E R T
US Instruction Manual
Power Supply and Regenerative Unit
Type R6-S
Type 25R6S3R-R00A
Mat.No.
Rev.
00R6SUB-KR01
1A

Advertisement

Table of Contents
loading

Summary of Contents for KEB COMBIVERT R6-S Series

  • Page 1 C O M B I V E R T US Instruction Manual Power Supply and Regenerative Unit Type R6-S Type 25R6S3R-R00A Mat.No. Rev. 00R6SUB-KR01...
  • Page 3: Table Of Contents

    Table of Contents Table of Contents Introduction ..................... 5 Preface ..........................5 Product description ......................5 Validity and liability ......................7 Copyright ..........................7 1.5 Specified application ......................7 1.5.1 Standard operation ........................7 1.5.2 Abnormal operation .......................8 1.6 Unit identification ........................8 Safety Instructions ..................9 General instructions ......................9 Transport, storage and installation ..................9 Electrical connection ......................10 Technical Data ....................
  • Page 4 Figure 8: Fuse holder ......................26 Figure 9: EMC-compatible control cabinet installation ............27 Figure 10: General description of input terminals at KEB inverter ...........29 Figure 11: Description of the input terminals of the COMBIVERT R6 ........30 Figure 12: Connection terminals of the power circuit ...............31 Figure 13: Connection terminals of the control board ..............32...
  • Page 5: Introduction

    Introduction Preface First we would like to welcome you as a customer of KEB and congratulate you on the purchase of this product. You have decided on a product of the highest technical innovation. The enclosed documents as well as the specified hardware and software are developments of KEB. KEB has created these documents, hardware, and software and they are to the best of KEB’s knowledge error free.
  • Page 6: Figure 1: Block Diagram Of The Combivert R6S

    Introduction Interface communi- cation Connection syn- Control communication I / O chronization (net- Connection work coverage) Power unit X1B L1 X1A ++ X1C L1 X1A L12 X1C Fo.1 X1A L22 X1C Fo.2 X1A L32 X1C L2 X1B L2 X1A -- Figure 1: Block diagram of the COMBIVERT R6S US - 6...
  • Page 7: Validity And Liability

    The customer may use the instruction manual as well as further enclosed documents or parts from it for internal purposes. KEB has the copyrights and they remain effective also to the full extent. All rights reserved. KEB®, COMBIVERT®, KEB COMBICONTROL® and COMBIVIS® are registered trademarks of KEB Automation KG.
  • Page 8: Abnormal Operation

    At factory setting the modulation is switched off in case of a net phase failure and error message E.nEt is dis- played. Special adjustments from KEB are necessary if the modulation and/or the standard operation should start again within a defined time in case of return of power supply.
  • Page 9: Safety Instructions

    Safety Instructions Safety Instructions General instructions The COMBIVERT R6 power supply and recovery unit contains dangerous voltages which can cause death or serious injury. The COMBIVERT R6 can be adjusted such that energy is returned to the line supply system even in case of power failure during generator operation.
  • Page 10: Electrical Connection

    620, the power semiconductor of the unit and existing radio interference filters must be disconnected because of the danger of destruction. This is permissible in compliance with Insulation the standard, since all units are given a high voltage test during the quality testing at KEB Measurement in accordance with EN 50178.
  • Page 11 Ground the cabinet or the system with the shortest connection to the main ground point (avoid ground loops) • Use exclusively the commutation choke or harmonic filter specified by KEB. • The average value of the supplied DC current may not exceed the maximum DC current.
  • Page 12 Proof With applications requiring the COMBIVERT R6 to be switched on and off cyclically, maintain an off-time of at least 5 min. If you require shorter cycle times please contact KEB. Switching Cyclic Turn off during the initialization phase can cause undetermined conditions.
  • Page 13 EMC directive are complied with. The prescribed ratings can usually be complied with when using the radio interference voltage filters as specified by KEB, and when observing the following measures and installation guidelines.
  • Page 14: Technical Data

    At uncontrolled B6 converters the phase angle cosφ1 can be set to one, so the value of the fundamental frequency components is equal to the value of the power factor. Please contact KEB for higher values. US - 14...
  • Page 15: Overload (Ol) Function

    Technical Data Connection to IT and delta power systems after consultation KEB. Voltage stabilization must be activated at the inverter if a harmonic filter is used. If a harmonic filter is used, volt- age stabilization must be activated for the inverter which is connected to the DC circuit.
  • Page 16: Operating Conditions

    Technical Data Operating conditions Standard Standard/ Instructions class EN 61800-2 Inverter product standard: rated specifications Definition according to EN 61800-5-1 Inverter product standard: general safety max. 2000 m above sea level (with site altitudes over 1000 m a derating of Site altitude 1 % per 100 m must be taken into considera- tion)
  • Page 17: Accessories

    Technical Data Accessories Unit size Rated voltage 400 V Commutation choke 25Z1B04-1000 00R6940-2407 Synchronization unit Control cabinet installation; max. distance to the power supply and regenerative unit 1m 00F50C3-4010 Length 1 m Sync cable for connection of the synchronization unit with R6 regenerative unit US - 17...
  • Page 18: Options

    Fuse holder for NH00 0090574-0001 and NH000 fuses 25Z1C04-1000 Harmonic filter Please contact KEB for data to the THD value at regenerative (no UL certification) operation in accordance with EN 61800-2-12. Compliance with the IEEE519 requirements at a 480V / 60Hz Harmonic filter...
  • Page 19: Ferrite Rings

    Technical Data 3.4.1 Ferrite rings Ferrite rings are used for the reduction of the cable-based and radiated interferences. For high damping, the ferrite rings are attached as close as possible to the interference source, i.e. at the DC bus connections and at the motor output terminals of the frequency inverter. The conductors must be passed through the ferrite core for use as a current-compensated choke.
  • Page 20: Dimensions And Weights

    Dimensions and weights 3.5.1 Dimensions air cooling system mounted version Weight: 25 kg Figure 3: COMBIVERT R6 with fan heat sink US - 20...
  • Page 21: Commutation Reactor / Mains Choke

    3.5.2 Commutation reactor / mains choke Inductance Frequency Weight Mat.-Number [mH] [Hz] [kg] 25Z1B04-1000 0,133 45…65 Type and cross-section of the terminals Maximum tightening torque Stay bolt for ring thimble 25 Nm 200 lb inch Ø8 Hole for screw M8 Figure 4: Mains choke US - 21...
  • Page 22: Radio Interference Filter (Side-Mounted)

    3.5.3 Radio interference filter (side-mounted) Input Input Output L3 ` L2 ` L1 ` Weight Mat.-Number [Hz] [kg] 24E6T60-3000 3x480 50 / 60 ± 2 Type and cross-section of the terminals/- Maximum tightening torque cable M10 stay bolt for ring thim- 35 Nm / 310 lb inch Terminals L1, 35...95 mm²...
  • Page 23 PE Stud M10 1000 Weight Mat.-Number [Hz] [kg] 25E4T60-1001 3x480 50/60 Type and cross-section of the terminals/- Maximum tightening torque cable M10 stay bolt for ring thim- 37 Nm 320 lb inch Connection each 3 x 70 mm² (AWG 2/0) cable Figure 6: Radio interference filter 25E4T60-1001 (side-mounted)
  • Page 24: Synchronization Unit

    3.5.4 Synchronization unit A (1 : 1) 49,5 105,5 65,5 45,5 Line Max. tightening Part number Weight Terminal connection length torque M6 stay bolt for 4.5 Nm / 40 Ib ring thimble inch 00R6940-2407 0.65 kg M4 ring cable lug L1.1, L2.1, L3.1 240 mm (AWG 16)
  • Page 25: Fuse Holder With Cover

    3.5.5 Fuse holder with cover Dimensions: 4,96" 126 mm 1,57" 40 mm 1,34" 34 mm 0,5" 13 mm 0,75" 19 mm 3,15" 80 mm 0,12" 3 mm 1,81 " 46 mm 2,91" 74 mm 0,26" 6,5 mm 0,6" 15,5 mm 0,63"...
  • Page 26: Installation

    Installation Installation EMC-compatible control cabinet installation Mains fuse Main contactor EMC side-mounted filter (≥ size 25 R-S or R6-N) EMC sub-mounted filter (≤ size 19 R6-S) If necessary, external voltage limi- tation / synchronisation Commutation choke / harmonic filter 150 mm COMBIVERT R6 150 mm if necessary external DC fuses...
  • Page 27: Connection Of The Combivert R6

    DC bus. The supply source (supply unit or inverter with AC input) must be suitable for this value. Terminals Description of terminals at KEB inverters ++, – – DC voltage input with starting current limiting; usable as output only if all units supplied by the DC bus have a starting current limiting at the DC voltage input.
  • Page 28: Connection Terminals Of The Power Circuit

    L3.2 X1C L2 X1B L2 Terminals Description of terminals at KEB inverters ++, – – DC voltage output with starting current limiting for loading the connected inverters; usable as input for regenerative operation. If inverters with mains supply of type A1 or A2 (see 4.3.1) are available in the DC bus, these may be switched to mains only after loading the DC bus.
  • Page 29 Fo.1 Fo.2 L1.2 L2.2 L3.2 Termi- Name Function L1.2, L2.2, L3.2 3-phase mains connection to the commutation choke DC voltage output with starting current limiting; Connection for ++, – – the inverter, the connection terminals are each internally con- nected in parallel. Fo.1, Fo.2 NC contact for safety monitoring (250 Vac /2 A, 24 Vdc / 0.4 A L1, L2...
  • Page 30: Connection Power Unit R6-S With Ul

    Connection power unit R6-S with UL 4.4.1 Power supply and regenerative operation at inverter current ≤ inverter current of one COMBIVERT R6-S with UL 24VDC Control voltage Sync L1.1 L1.2 L2.1 L2.2 L3.1 L3.2 L1.2 L2.2 L3.2 17 18 24 25 24 26 K2 K2 L1 L2 13 14 Uout COM RLA RLB 25R6S3R -xxxx Fo1 Fo2 Ferrite...
  • Page 31: Power Supply And Regenerative Operation At Parallel Operation With One Frequency Inverter

    Pre-charging contactor (400 V / 12 A AC3) Sync Synchronization unit (max. length of the phase lines 1 m) Commutation choke / harmonic filter Regenerative unit COMBIVERT R6-S Power circuit terminals Connection for line contactor Connection for precharging and DC fuse monitoring Control terminal strip (X2A.12: control release;...
  • Page 32: 4.4.4 Brief Description Of The Pre-Charging Sequence

    4.4.4 Brief Description of the Pre-Charging Sequence There are three switches coming from the external controller. S1 engages the contactor K0, which sub-sequentially engages contactor K2 for system pre- charging. This should be activated first. S2 enables the R6 unit given that K0 is already engaged. S3 enables the F5 drive given that there is not fault on the R6 unit.
  • Page 33: Connection Of The Control Board Version S

    *) The relay outputs must be operated with max. 48 V DC protective separation voltage to guar- antee the CE standard. After consultation with KEB a current of max. 2A DC is permissible for 120 V AC (depending on the switching capacity etc.).
  • Page 34: Assignment Of The Socket X2B

    4.5.2 Assignment of the socket X2B RJ45 socket for phase synchronization No. Name Function and temperature sensor Connection for temperature sen- sor (option) 3 U13_syn Synchronization phase 1 / 3 – reserved 5 U21_syn Synchronization phase 2 / 1 – reserved 7 U32_syn Synchronization phase 3 / 2 –...
  • Page 35: Wiring Example

    4.5.4 Wiring example In order to prevent a malfunction caused by interference voltage supply on the control inputs, the following directions should be observed: • Use shielded/drilled cables • Lay shield on one side of the inverter onto earth potential •...
  • Page 36: Operation Of The Unit

    Operation of the Unit Operation of the Unit Operation with PC and system software COMBIVIS 6 Instructions for the installation and operation of the system software COMBIVIS can be taken from the appropriate software instruction. See kebblog.com/elevator-support for videos. Switch-on procedure The COMBIVERT R6-S is initialized after connection of the power supply.
  • Page 37: Parameter Summary

    Parameter summary The CP parameters are the parameter selections defined by KEB. You need an application manual in order to get access to the entire parameter list. Display Parameter Setting range Resolution Factory setting CP.0 Password input 0…9999 – CP.1 Status display –...
  • Page 38: Monitoring And Analysis Parameters

    Approach of the working meters The displayed values of the working meters offer only an estimate value because of measurement and calculation inaccuracies. These displayed values are un- suitable for tariff applications and cannot replace any measuring devices. Monitoring and analysis parameters The following parameters serve for the functional monitoring during operation.
  • Page 39 Name Enter Origin CP.01 status display – – ru.00 E.SYn „ERROR synchronisation, phase allocation at commutation choke not correct E. UP „ERROR underpotential, DC link voltage too low Name Enter Origin CP.02 actual line frequency – – ru.03 After switching on, the actual mains frequency is determined during the initialization phase. Slow changes of the line frequency during the operation are recognized and displayed in CP.02.
  • Page 40 Name Enter Origin CP.08 DC current – – ru.15 Resolution Meaning 0.1 A Display of the calculated DC output current in ampere. Name Enter Origin CP.09 DC voltage – – ru.19 Resolution Meaning Display of actual DC link voltage in volt. The value is measured at the DC output terminals of the COMBIVERT R6-S.
  • Page 41 Name Enter Origin CP.13 active power – – ru.81 Resolution Meaning CP.13 displays the actual power of the COMBIVERT R6-S. Motor pow- 0.1 kW er is displayed with positive values, generatoric power is displayed with negative values. Name Enter Origin CP.14 total regen –...
  • Page 42: Special Adjustments

    Special adjustments The power supply and regenerative unit can be adapted to the application with the following parameters. Name Enter Origin CP.18 ANOUT 1 gain – An.33 The analog output displays the difference between actual supply frequency and set supply frequency.
  • Page 43 Name Enter Origin CP.21 last error – – In.24 set 0 CP.22 last error -1 – – In.24 set 1 CP.23 last error -2 – – In.24 set 2 CP.24 last error -3 – – In.24 set 3 CP.25 last error -4 –...
  • Page 44 Name Enter Origin CP.34 control angle – – Value range Meaning This parameter adjust the conduction angle during regen mode. By lowering this value, the audible sound from the commutation choke 0.0...60.0 may be reduced. If the value is too high or too low, available regen power may be limited and random E.OC errors can occur.
  • Page 45: Certification

    A.1.2 UL Certification Acceptance according to UL is marked at KEB power supply and regen- erative units with the adjacent logo on the type plate. To be conform according to UL for the use on the North American Market the following in- structions must be observed (original text of the UL file in English): •...
  • Page 46 +39 02 3353531 • fax: +39 02 33500790 net: www.keb.de • mail: kebitalia@keb.it KEB Power Transmission Technology (Shanghai) Co.,Ltd. No. 435 Qianpu Road, Chedun Town, Songjiang District, KEB Japan Ltd. CHN-Shanghai 201611, P.R. China 15–16, 2–Chome, Takanawa Minato-ku fon: +86 21 37746688 • fax: +86 21 37746600...

This manual is also suitable for:

Combivert 25r6s3r-r00a

Table of Contents