Protective functions
Message
Operator
E.buS/ A.buS
E.dOH/ A.dOH 9/96
E.EEP
E.EF/ A.EF
E.LSF
E.nEt
E.OC
E.OH/ A.OH
E.OHI/ A.OHI
E.OL/ A.OL
E.OP
E.PU
E.Puch
E.PucI
E.PUIN
E.SEt/ A.SEt
E.SYn
E.UP
F.nEt

3.6.1.1 Undervoltage

„Error! Undervoltage" (E.UP) is triggered if the DC link voltage drops due to brownouts or a generally too weak
power grid. For this error, the automatic restart can be activated.

3.6.1.2 Overvoltage

„Error! Overvoltage" is triggered if the DC link voltage increases beyond the overvoltage level.

3.6.1.3 Overcurrent

The „Error! Overcurrent" (E.OC) is triggered, if the „OC tripping current" (see technical data in the instruction
manual) is exceeded.
If this error occurs permanently, either the parameter setting is not correct or the COMBIVERT is defective.
Seite 3.6 - 4
Value
Message COMBIVIS
18/93
Error!/warning! watchdog
Error!/warning! temperature of the commutation choke
21
Error! EEPROM defective
31/90
Error!/warning! ERROR external fault
15
Error! load shunt fault
3
Error! Net
4
Error! overcurrent
8/89
Error!/warning! Power module temperature
6/87
Error!/warning! interior temperature
16/99
Error!/warning! overload (Ixt)
1
Error! overvoltage
12
Error! defective in power unit
50
Error! power unit code changed
49
Error! power circuit unknown
14
Error! power unit coding
39/102
Error!/warning! set
59
Error! synchronization
2
Error! underpotential
40
Error! mains frequency
COMBIVERT R6-S
Pre-warning period or level adjustable
Pre-warning possible via digital output
Function can be switched off
Automatic restart adjustable
Error without adjustable response
Unity of the pre-warning
-
-
s
-
s
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
°C
-
s
-
-
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
© KEB, 2008-02